| 技术数据 |
| Technology |
|
| On line double conversion |
| VFI (Voltage Frequency Independent) |
Input
|
|
| Voltage (configurable) |
3-phase 380 V - 400 V - 415 V |
| Tolerance |
400 V +/- 15 % |
| Frequency (configurable) |
50 / 60 Hz |
Tolerance
|
45 to 65 Hz |
| Power Factor |
0.93 ind. |
| Current distorsion DELPHYS MX elite |
THDI < 4,5 % |
| Output |
|
| Voltage (settable) |
3-phase 380 V - 400 V - 415 V |
| Tolerance (static condition) |
< 1 % |
| Tolerance (dynamic condition) on load impact 0 to 100 % |
+/- 2 % |
| Voltage distortion rate with non-linear loads |
Ph/N : < 3 % Ph/Ph : < 2.5 % |
| Frequency |
50 / 60 Hz |
| Inverter frequency tolerance |
+/- 0.2 % |
| Admissible overload mains off |
10 mn: 125 % 1 mn: 150 % |
| Admissible crest factor without downgrading |
up to 3 |
| PF admissible without downgrading |
0.1 ind to 0.9 cap. |
| Overall Efficiency |
up to 94 %* |
| In ECO-MODE configuration |
98 % |
| Environment |
|
| Colour |
grey |
| Sound level at 1 m |
< 72 dBA* |
|
Confity to standards
Safety
EMC
Performances
Classification as per IEC62040-3 |
IEC62040-1-2 IEC60950
IEC62040-2
IEC62040-3
ASI classe VFI - SS - 111
|
| * according to power |